Error Code Table for Vertex Ducted Central Split (DYC-18) SystemsUpdated 4 days ago

This article provides an error code table for Vertex Ducted Central Split (DYC-18) systems

Code
Failure or Protection Definition
ATL
Overtemperature protection
dC
Force Cooling mode
df
Defrost mode
d0
Oil return mode
E1Communication error (indoor unit)
E2T1 sensor error
E3T2 sensor error
E4Indoor refrigerant sensor detecting leakage error
E6Refrigerant leakage fault
E7Indoor control board chip failure or EEPROM failure (indoor unit)
E8Fan motor error or indoor fan protection (indoor unit)
E9Smart controller communication error
F0Communication failure (outdoor unit)
F4T4 outdoor ambient temperature sensor error
F5T5 exhaust temperature sensor error
F6T3 condenser temperature sensor error
F7T7 temperature sensor error
F8T7 temperature sensor error in detecting condensation risks
F9AC overvoltage or undervoltage protection
FAEEPROM failure (outdoor unit)
FBEEPROM failure of the driver chip
FCIPM module temperature fault
FDHLP pressure sensor failure
FET3 or T5 sensor disconnect error
FFHigh pressure switch disconnection
H0
Communication fault of the master board and driver chip
H1
T3 sensor high temperature error (Cooling mode) 
(Three times P5 error within 180 minutes)
H2
High pressure switch error 
(Three times P1 error within 150 minutes)
H3
High pressure abnormal failure protection (Heating mode)
(Three times PD error within 180 minutes)
H4
IPM modular high temperature error
(Three times P8 within 120 minutes)
H5
Low pressure abnormal failure protection
(Five times P2 within 240 minutes)
H6
T5 exhaust temperature too high protection
(Three times P4 within 100 minutes)
H7
Wet operation error
(Three times PC within 200 minutes)
H8
T3 condenser sensor disconnect error
(Three times FE within 120 minutes)
HC
Discharge temperature sensor disconnect error 
(Three times FE within 180 minutes)
HE
Condensate error
(Three times within 60 minutes)
L0
DC cable bus low-voltage protection
L1
DC cable bus high-voltage protection
LA
Frequency limitation by voltage
LB
Frequency limitation or decline by high pressure
LC
Frequency limitation by condenser temperature
LD
Frequency limitation by discharge temperature
LE
Frequency limitation by IPM modular high temperature
LF
Frequency limitation by current
P1High pressure switch protection
P2Low pressure abnormal failure protection
P3Overcurrent protection of the primary side or secondary side
P4T5 exhaust temperature too high protection
P5T3 outdoor coil temperature over-high protection (Cooling mode)
P6IPM module protection
P7T2 freeze protection
P8IPM high temperature protection (Ft)
P9DC fan malfunction
PCWet operation malfunction
PDHigh pressure abnormal failure protection (Heating mode)