E4 Error CodeUpdated 3 days ago
Introduction
The "E4" error code indicates an indoor refrigerant sensor detects leakage error. This article is for Vertex Ducted Central Split (DYC-18) systems.
The error code shows on the wired controller display.
Cause: Sensor reading error.
Troubleshooting Diagram
Troubleshooting Notes
- Confirm whether the sensor is firmly connected and check the sensor connector to ensure that it is firmly connected.
- Unplug the sensor and use a multimeter to measure the resistance to check whether it is an open circuit or short circuit. If so, replace the sensor. If not, replace the main control board.