P7 Error CodeUpdated 4 days ago

Introduction

The "P7" error code indicates T2 freeze protection. This article is for Vertex Ducted Central Split (DYC-18) systems

Cause: The T2 detection temperature is too low. The T2 sensor detects the temperature is less than 32°F (0°C). 

Troubleshooting Diagram

Troubleshooting Notes

  • Begin by confirming whether the indoor coil is frozen. If it is frozen, check the pipe system. If there is no icing, check the T2 sensor or the indoor board.
  • Measure the resistance of the T2 temperature sensor and check whether it drifts by comparing it with the resistance table. If it drifts, replace the sensor. 
  • Replace the indoor board. 