FE & H8 Error CodesUpdated 4 days ago
Introduction
The "FE" and "H8" error codes indicate a T3 or T5 sensor disconnect error. This article is for Vertex Ducted Central Split (DYC-18) systems.
Cause: The probe is in the wrong position.
Troubleshooting Diagram
Troubleshooting Notes
- Check whether the positions of the T3 and T5 probes have changed. For example, if the exhaust probe T5 falls out, the measured temperature is not the real exhaust temperature.
- Check whether the T3 and T5 probes are installed in the correct position on the pipe. Eliminate the possibility of a wrong installation.
- Use a multimeter to measure the sensor resistance to see if the sensor is damaged.
- If all of the above is OK, replace the main control board of the external unit.