Error Code Table for Diamante & Quantum Series SystemsUpdated 4 days ago

This article provides an error code table for Diamante and Quantum series systems. 

CodeReasonRemark
bc
PM2.5 sensor failure
(Indoor unit failure, optional)
Query by pressing the remote controller
bf
TVOC sensor failure
(Indoor unit failure, optional)
Query by pressing the remote controller
bj
Humidity sensor failure
(Indoor unit failure)
Query by pressing the remote controller
CL
Filter duty reminder
Clean the air filter, then cut off the power supply again
E0Indoor unit and outdoor unit communication failureIs the wiring connection of the indoor unit and outdoor unit correct? 
E1Indoor unit room temperature sensor failure
(Indoor unit room temperature failure)
Indoor unit sensor and PCB
E2Indoor unit coil temperature sensor failure
(Indoor unit pipe (coil) temperature failure)
Indoor unit sensor and PCB
E3Outdoor unit coil temperature sensor failure
(Outdoor pipe temperature)
Outdoor unit coil sensor and PCB
E4AC-cooling system abnormalGas leakage?
2-way or 3-way valve blocked?
E5Indoor unit or outdoor unit mismatched failure
(specifically performance test on the production line) 
/
E6Indoor unit PG fan motor or DC fan motor abnormal operation
(Indoor unit failure)
Fan motor, fan blade, and PCB
E7Outdoor unit ambient temperature sensor failureOutdoor unit ambient sensor and PCB
E8Outdoor unit discharge temperature sensor failureOutdoor unit discharge sensor and PCB
E9
Diamante

Quantum
IPM or compressor driving control abnormalOutdoor unit PCB, compressor, etc.
EAOutdoor unit current test circuit failureIs the outdoor unit PCB broken?
EbAbnormal communication of the main PCB and display board
(Indoor unit failure)
Display board and main PCB
EEOutdoor unit EEPROM failure1. Is the outdoor unit PCB broken?
2. Try to re-power on the AC unit
EFOutdoor unit DC fan motor failureFan motor and outdoor unit PCB
EHSuction temperature sensor failure/
EnGas pipe temperature sensor failure/
EU
Outdoor unit voltage test sensor fault
Outdoor unit PCB
EyLiquid pipe temperature sensor failure/
F0
Infrared customer feeling test sensor failure
(Indoor unit failure)
Query by pressing the remote controller
F1
Electric power test module failure
(Indoor unit failure)
Query by pressing the remote controller
F2
Discharge temperature sensor failure protection
Check the troubleshooting for details
F3
Outdoor unit coil temperature failure protection
Check the troubleshooting for details
F4
Cooling system gas flow abnormal protection
Check the troubleshooting for details
F5
PFC overcurrent protection
Check the troubleshooting for details
F6
Diamante

Quantum
Compressor lack of phase or anti-phase protection
Check the troubleshooting for details
F7
IPM over-temperature protection
Check the troubleshooting for details
F8
4-way value reversing abnormal
Check the troubleshooting for details
F9
Module temperature test circuit failure
Outdoor unit PCB
FA
Compressor phase-current test circuit failure
Outdoor unit PCB
Fb
Limiting or reducing frequency for overload protection in Cooling or Heating mode
Query by pressing the remote controller
FC
Limiting or reducing frequency for high-power consumption protection
Query by pressing the remote controller
Fd
Refrigerant detector failure
Check the troubleshooting for details
FE
Limiting or reducing frequency for module current protection
(phase current of compressor)
Query by pressing the remote controller
FF
Limiting or reducing frequency for module temperature protection
Query by pressing the remote controller
FH
Limiting or reducing frequency for compressor driving protection
Query by pressing the remote controller
Fj
Limiting or reducing frequency for discharge over-temperature protection
Query by pressing the remote controller
Fn
Limiting or reducing frequency for outdoor unit AC-current protection
Query by pressing the remote controller
FP
Limiting or reducing frequency for anti-condensation protection
Query by pressing the remote controller
FU
Limiting or reducing frequency for anti-frost protection
Query by pressing the remote controller
H1
High pressure switch failure (Multi-Zone units only)
/
H2
Low pressure switch failure (Multi-Zone units only)
/
Hd
Leak detector of the indoor unit detects refrigerant
/
Fy
Gas leakage protection
Query by pressing the remote controller
P0IPM protectionOutdoor unit PCB
P1Over or under-voltage protection1. Is the outdoor unit PCB broken?
2. Is the power supply abnormal?
P2Over-current protection1. Is the outdoor unit PCB broken?
2. Is the power supply abnormal?
P4
Diamante

Quantum
Outdoor unit discharge temperature overheating protectionCheck the troubleshooting for details
P5Sub-cooling protection in Cooling modeCheck the troubleshooting for details
P6Overheating protection in Cooling modeCheck the troubleshooting for details
P7Overheating protection in Heating modeCheck the troubleshooting for details
P8Outdoor over-temperature or under-temperature protectionCheck the troubleshooting for details
P9Compressor driving protection (Load abnormal)Check the troubleshooting for details
PACommunication failure for the top flow unit or preset mode conflict 
(Multi-Zone units only)
Check the troubleshooting for details