Select the Indoor Unit Installation Location for Quantum Fresh (WYT-FA) SystemsUpdated 13 days ago

Introduction

This article explains how to select the installation location for indoor units of Quantum Fresh (WYT-FA) systems

Install the indoor unit inside the room intended for air conditioning. Avoid corridors and communal areas. 

Note: Select the positions of both the indoor and outdoors units before starting the installation. Follow the minimum clearance requirements for both the indoor and outdoor units. 

Select the Location

Follow the tolerances depicted in the illustration below: 

Due to the fresh air + gentle wind mechanism, the model is designed without fingerguards. For safety reasons, the indoor unit's louver must be located at a safe height of 8.2 feet (2.5 m) or more above the floor. If the system is installed at a shorter height, any injury incurred from sticking fingers into the airflow louver is the responsibility of the installer or user. 

Follow these best practices for selecting an optimal space for installing the indoor unit: 

  • Do not install the unit on a wall that is subject to vibrations. 
  • Do not install the system near sources of heat, steam, or flammable gases. 
  • Do not install the indoor unit in a location that is exposed to direct sunlight. 
  • Ensure that the inlet and outlet vents are not obstructed. The system should be able to output air all across the room. 
  • Minimize the distance between the indoor and outdoor units. Install the system in a location where connecting the indoor and outdoor units will be as simple as possible. 
  • Install the unit on a strong wall and where it is easy to drain the condensate water. 
  • Install the unit in a location where it will be easy to service the product and perform any necessary maintenance. 

Installation Diagram

Outdoor Above Indoor Unit

Indoor Above Indoor Unit

  • Install the indoor unit so that its bottom is at least 8.2 feet (2.5 m) above the floor. 
  • Ensure adequate space above the air handler for return airflow (4-6 inches, ideally 8 inches / 102-152 mm, ideally 203 mm). 

Fresh Air Inlet

  • Keep the fresh inlet within 14 inches (355.6 mm) of the wall. 
  • Rotate the pipe as needed to avoid interference with other lines. 
  • Ensure a slight downward slope to prevent rain intrusion. 
  • Maintain a minimum bend radius of 2-3/8 inches (60 mm) to preserve airflow. 
  • Do not place the inlet near exhaust outlets, enclosed areas, or polluted air sources. 