Parameter Check Table for Vertex Ducted Central Split (DYC-18) SystemsUpdated 4 days ago

Introduction

This article provides the parameter check table for Vertex Ducted Central Split (DYC-18) systems

To display the system parameters, press the "Check" (K4) button to index through the series of parameters available. 

Press the "Check" button one time to have the system's display board show the sequence. After 1 second, the display board will show the value of the parameter. 

When the "Check" button is pressed again, the display board will show the next sequence. 

After staying on the same parameter for 20 seconds, the display board will revert back to its normal status. 

Parameter Check Table

No.Display Content
00Outdoor mode (0: Standby mode / 2: Cooling mode / 3: Heating mode)
01Outdoor power (model)
02Running mode (0: Standby mode / 2: Cooling mode / 3: Heating mode)
03Target frequency (Hz; Actual value)
04Actual frequency (Hz; Actual value)
05Running frequency (Hz; Actual value)
06T3 condensing temperature (°F; Actual value)
07T4 outdoor ambient temperature (°F; Actual value)
08T5 exhaust temperature (°F; Actual value)
09Temperature transform by pressure sensor (°F; Actual value)
10IPM modular temperature (°F; Actual value)
11Target temperature Tes / Tcs (°F; Actual value)
12Discharge temperature superheat (°F; Actual value)
13Target superheat (°F; Actual value)
14Fan speed (Actual value / 10)
15EXV opening degree (Step; Actual value)
16Pressure value (PSI; Actual value * 25)
17Pressure valve transform by T3 (PSI; Actual value * 25)
18AC voltage (VAC; Actual value)
19DC voltage (VDC; Actual value)
20AC current (A; Actual value)
21Compressor current
22Oil output (CC; Actual value)
23T1 indoor ambient temperature (°F; Actual value)
24T2 indoor evaporator temperature (°F; Actual value)
25Concentration value
26Enter PI control sign (0 or 1)
27Enter defrosting type
28Test mode (1-40; Mode gear)
29Frequency increase (Shift; Actual value)
30EV (Step; Actual value)
31PFC control state
32Frequency limit item
33Driving failure code subdivision 1
34Driving failure code subdivision 2
35Last failure or protection code
36Software version number (1-255)
37T7 condensing temperature (°F; Actual value)
38T30 temperature (°F; Actual value)
39Compressor ratio


Meaning of Item 33 in Parameter Check Table

Display Information
Meaning
Remarks
1Compressor overcurrent
(Triggered by the internal comparator of the chip)
Lower-level code
of P6
2Compressor hardware overcurrent
(Triggered by the IPM module FO or external comparator)
3Compressor stall protection
4Compressor blockage protection
5Compressor overcurrent (software detection)
7Compressor sampling circuit abnormality (bias)
8Compressor phase loss protection
9Compressor weak magnetic voltage protection
21Drive E faultFB
22Module temperature sensor malfunctionFD
61Bus voltage low protectionL0
62Bus voltage high protectionL1


Meaning of Item 34 in Parameter Check Table

Display InformationMeaningRemarks
1-8Specific causes of faults in fansLower-level code of P9
11-14Sensor malfunctionReference Outdoor Unit Error Codes