Display the current indoor temperature on Diamante Ultra Series systemsUpdated 4 hours ago
Introduction
Learn how to get your wall-mounted WYT-22 Diamante Ultra Series system to display the current room temperature detected by the indoor unit.
Steps
- Power On the remote controller.
- Press the “Fan”, “Mode”, and “Up-Down Swing” buttons together simultaneously for at least 5 seconds. The remote control will display “00” and enter the parameter inquiry function.
- Press the temperature setting button to change the value.
- Select “01” as the desired parameter. Note: Refer to the General Parameter Code List section for additional information on parameter codes.
- Press the “Mode” button while pointing the remote controller towards the indoor unit. The indoor unit will display the corresponding parameter for 30 seconds.
- Power Off the remote controller to exit the inquiry interface.
General Parameter Code List
The following is a general parameter code list:
Note: Some models might not have these parameters.
- 01: Indoor room temperature
- 02: Indoor coil temperature
- 03: Outdoor temperature
- 04: Outdoor coil temperature
- 05: Compressor discharge temperature
- 06: Unit running current
- 07: Display error code (if there is no error code, display '--')
- 11: Compressor frequency
- 12: Indoor fan speed
- 13: Outdoor fan speed
- 14: Compressor current
- 15: Expansion valve opening degree