Specifications for Refrigerant PipingUpdated an hour ago

Introduction

This article provides refrigerant piping specifications for different systems.

Notes

  • The length of the refrigerant piping will affect the performance and energy efficiency of the unit. 
  • Nominal efficiency is tested on units with a pipe length of 16 feet (4.9 m). 
  • The factory precharge supports up to 25 feet (7.6 m) of connection lineset. 
  • The total piping length should not be less than 10 feet (3 m).
  • If the factory precharge is modified, make a note of the charge modification amount. 

Specifications

Refer to these tables for the specifications of the refrigerant piping, such as the maximum piping length and drop height:

Diamante Essenza High-Wall

WYT-17
Model / Capacity (BTU/h)
11.5K BTU
(110~120V)
11.5K BTU
(208~230V)
17K BTU23K BTU35K BTU
RefrigerantR32R32R32R32R32
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 3/8 inchØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m100 ft / 30.5 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m33 ft / 10 m50 ft / 15.2 m65 ft / 19.8 m


Diamante Pro High-Wall

WYT-20
Model / Capacity (BTU/h)
9K BTU
(110~120V)
9K BTU
(208~230V)
12K BTU
(110~120V)
12K BTU
(208~230V)
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 3/8 inchØ 3/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m33 ft / 10 m33 ft / 10 m


WYT-20
Model / Capacity (BTU/h)
18K BTU24K BTU31.5K BTU36K BTU
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 1/2 inchØ 5/8 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units65 ft / 19.8 m65 ft / 19.8 m100 ft / 30.5 m100 ft / 30.5 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m65 ft / 19.8 m


Quantum Ultra High-Wall

WYT-24
Model / Capacity (BTU/h)
9K BTU
(110~120V)
9K BTU
(208~230V)
12K BTU
(110~120V
12K BTU
(208~230V)
18K BTU24K BTU
RefrigerantR-454BR-454BR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 3/8 inchØ 3/8 inchØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m33 ft / 10 m33 ft / 10 m50 ft / 15.2 m50 ft / 15.2 m


Quantum Hyperformance High-Wall

WYT-25
Model / Capacity (BTU/h)
9K BTU12K BTU18K BTU24K BTU
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m50 ft / 15.2 m50 ft / 15.2 m


Quantum Fresh High-Wall

WYT-FA
Model / Capacity (BTU/h)
12K BTU
RefrigerantR32
Liquid Pipe DiameterØ 1/4 inch
Gas Pipe DiameterØ 3/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m


Quantum Ultra Ceiling Cassette

CYT-24
Model / Capacity (BTU/h)
9.5K BTU12K BTU16K BTU23K BTU
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m50 ft / 15.2 m50 ft / 15.2 m


CYB-20
Model / Capacity (BTU/h)
36K BTU48K BTU
RefrigerantR-454BR-454B
Liquid Pipe DiameterØ 3/8 inchØ 3/8 inch
Gas Pipe DiameterØ 3/4 inchØ 3/4 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units250 ft / 76 m250 ft / 76 m
Adjustment Refrigerant Charge
(For each additional foot after 25 feet)
0.32 oz/ft0.32 oz/ft
Max. Drop Height Between the 
Indoor & Outdoor Units
100 ft / 30.5 m100 ft / 30.5 m


Quantum Ultra Single-Way Ceiling Recessed Cassette

CYK-24
Model / Capacity (BTU/h)
9K BTU12K BTU18K BTU
RefrigerantR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 1/2 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units80 ft / 24.4 m80 ft / 24.4 m100 ft / 30.5 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.16 oz/ft0.16 oz/ft0.16 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m


Quantum Ultra Floor/Low-Wall Mounted Console

FYB-24
Model / Capacity (BTU/h)
12K BTU16K BTU
RefrigerantR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 1/2 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.16 oz/ft0.16 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m50 ft / 15.2 m


Quantum Ultra Floor-Ceiling Flex

UYT-24
Model / Capacity (BTU/h)
18K BTU22K BTU
RefrigerantR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units65 ft / 19.8 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m


UYB-20
Model / Capacity (BTU/h)
36K BTU48K BTU
RefrigerantR-454BR-454B
Liquid Pipe DiameterØ 3/8 inchØ 3/8 inch
Gas Pipe DiameterØ 3/4 inchØ 3/4 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units250 ft / 76 m250 ft / 76 m
Adjustment Refrigerant Charge
(For each additional foot after 25 feet)
0.32 oz/ft0.32 oz/ft
Max. Drop Height Between the 
Indoor & Outdoor Units
100 ft / 30.5 m100 ft / 30.5 m


Quantum Ultra Ducted Ceiling Concealed

RYT-24
Model / Capacity (BTU/h)
9.5K BTU11K BTU17K BTU22K BTU
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 1/4 inchØ 1/4 inchØ 1/4 inchØ 1/4 inch
Gas Pipe DiameterØ 3/8 inchØ 3/8 inchØ 1/2 inchØ 5/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m65 ft / 19.8 m65 ft / 19.8 m
Adjustment Refrigerant Charge
(For each additional foot after 25 ft)
0.11 oz/ft0.11 oz/ft0.11 oz/ft0.11 oz/ft
Max. Drop Height Between the Indoor & Outdoor Units33 ft / 10 m33 ft / 10 m50 ft / 15.2 m50 ft / 15.2 m


RYB-20
Model / Capacity (BTU/h)
36K BTU48K BTU
RefrigerantR-454BR-454B
Liquid Pipe DiameterØ 3/8 inchØ 3/8 inch
Gas Pipe DiameterØ 3/4 inchØ 3/4 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units250 ft / 76 m250 ft / 76 m
Adjustment Refrigerant Charge
(For each additional foot after 25 feet)
0.32 oz/ft0.32 oz/ft
Max. Drop Height Between the 
Indoor & Outdoor Units
100 ft / 30.5 m100 ft / 30.5 m


Vertex Ducted Central Split

DYC-18
Model / Capacity (BTU/h)
24K BTU34K BTU47.5K BTU55.5K BTU
RefrigerantR-454BR-454BR-454BR-454B
Liquid Pipe DiameterØ 3/8 inchØ 3/8 inchØ 3/8 inchØ 3/8 inch
Gas Pipe DiameterØ 3/4 inchØ 3/4 inchØ 7/8 inchØ 7/8 inch
Max. Length of the Piping with Standard Charge25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m25 ft / 7.6 m
Max. Length Between the Indoor & Outdoor Units100 ft / 30.5 m100 ft / 30.5 m100 ft / 30.5 m100 ft / 30.5 m
Max. Drop Height Between the Indoor & Outdoor Units50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m50 ft / 15.2 m