R-454B Refrigerant Charging TablesUpdated 4 days ago

Introduction

This article provides charge and area requirements for systems that use R-454B refrigerant. 

The following systems use R-454B refrigerant:

  • Diamante Pro (WYT-20)
  • Quantum Ultra High-Wall (WYT-24)
  • Quantum Hyperformance (WYT-25)
  • Quantum Ultra Ceiling Cassette (CYT-24)
  • Quantum Ultra Ducted Ceiling Concealed (RYT-24)
  • Quantum Ultra Floor-Ceiling Flex (UYT-24)
  • Vertex Ducted Central Split (DYC-18)

Maximum Charge

CategoryLFL
(kg/m3)
h0
(m)
Floor Area (m2)
Maximum Charge (kg)
471015203050
R-454B0.2960.60.360.620.891.271.461.792.32
10.591.041.482.112.442.993.86
1.81.071.862.663.814.395.386.95
2.21.32.283.264.655.376.588.49
2.61.542.693.855.56.357.7710.03
3.01.783.114.44
6.347.328.9711.58


Minimum Room Area

CategoryLFL
(kg/m3)
h0
(m)
Charge Amount (M) (kg)
Minimum Room Area (m2)
1.776 kg2.664 kg3.552 kg5.328 kg7.104 kg8.88 kg11.544 kg
R-454B0.2960.6/66.17117.63264.68470.54735.211,242.51
1/23.8242.3595.28169.39264.68447.3
1.8/1013.3329.4152.2881.69138.06
2.2/8.1810.9119.693554.6992.42
2.6/6.929.2314.1025.0639.1566.17
3.0/6.08.012.018.8229.4149.70