R-32 Refrigerant Charging TablesUpdated 4 days ago

Introduction

This article provides charge and area requirements for systems that use R-32 refrigerant. 

The following systems use R-32 refrigerant:

  • Diamante Essenza (WYT-17)
  • Quantum Fresh (WYT-FA)

Maximum Charge

CategoryLFL
(kg/m3)
h0
(m)
Floor Area (m2)
Maximum Charge (kg)
471015203050
R-320.3060.60.680.91.081.321.531.872.41
11.141.511.82.22.543.124.02
1.82.052.713.243.974.585.617.254
2.22.53.313.964.855.66.868.85


Minimum Room Area

CategoryLFL
(kg/m3)
h0
(m)
Charge Amount (M) (kg)
Minimum Room Area (m2)
1.224 kg1.836 kg2.448 kg3.672 kg4.896 kg6.12 kg7.956 kg
R-320.3060.6/2951116206321543
1/10194274116196
1.8/3613233660
2.2/249152440