PC0L Error CodeUpdated 2 hours ago
PC0L Error Code: Outdoor Unit Low Ambient Temperature Protection
This is a low ambient temperature protection function.
If the compressor is off and the outdoor ambient temperature (T4) remains below -31°F (-35°C) for 10 seconds, the system stops and displays a fault code.
If the compressor is on and T4 remains below -40°F (-40°C) for 10 seconds, the system stops and displays a fault code.
When T4 remains at or above -26°F (-32°C) for 10 seconds, the system exits protection mode.