Understand the Refrigerant Leak Detection FunctionUpdated 3 days ago
This article explains the refrigerant leak detection function for Vertex Ducted Central Split (DYC-18) systems.
This function utilizes a R-454B refrigerant sensor to detect refrigerant concentration.
If refrigerant leakage occurs in the indoor coil and the concentration is above 10%, the unit will do the following:
- Cut off the power to the thermostat in order to stop the compressor from continuing operation.
- Turn off the electric heat kit.
- Output high voltage between Terminal F and Terminal L2.
- Trigger the alarm.