Understand the Compressor Crankshaft Heater Control FunctionUpdated 13 days ago

This article explains the Compressor Crankshaft Heater Control function for Vertex Ducted Central Split (DYC-18) systems. 

The crankshaft heater will start if one of the following conditions are met: 

  • The compressor discharge temperature of the T5 sensor is less than 73°F (23°C) and the defrost function turns on. 
  • The compressor discharge temperature of the T5 sensor is less than 73°F (23°C) when powered on for the first time. 
  • The power off duration is longer than 3 hours or more than 2 hours when powered on for the first time. 

The function will deactivate when the following conditions are met:

  • The compressor discharge temperature of the T5 sensor is more than or equal to 82°F (28°C). 