Cable Wire Specifications for Diamante Pro SystemsUpdated 3 days ago
Introduction
This article provides the cable wire specifications for Diamante Pro (WYT-20) systems.
The power wire sizes assume the largest allowable fuse. 115V systems take a single-pole breaker for the main circuit panel. 
230V systems require a double-pole breaker, tandem-type breakers will not work. 
Consult the nameplate on the system for detailed electrical specifications.
Cable Wire Specifications
| Diamante Pro (WYT-20) | Section Area (AWG) | |||||
| 9K/12K (115V) | 9K/12K (230V) | 18K | 24K | 30K/36K | ||
| Power Supply Cable | N (L2) | 12 AWG | 14 AWG | 12 AWG | 12 AWG | 10 AWG |
| L (L1) | ||||||
![]() | ||||||
| Connection Cable for Communication Between Indoor and Outdoor Units | 3 (L) | 16 AWG | 16 AWG | 16 AWG | 16 AWG | 16 AWG |
| 2 (N) | ||||||
| 1 (S) | ||||||
![]() | ||||||