Connect the Indoor Unit Condensate Piping for Quantum Ultra Ducted Ceiling Concealed (RYT-24) SystemsUpdated 2 hours ago
Introduction
This article explains how to connect the indoor unit condensate piping for Quantum Ultra Ducted Ceiling Concealed (RYT-24) systems.
Notes
- Insulate all drain piping and connections to the indoor unit to prevent dew formation and dripping.
- Maintain a continuous downward slope of less than 1/4 per foot (76 mm), with no dips, sags, or reverse slopes. The minimum slope ratio is 1/50.
- Install support straps/brackets every 5-6.5 feet (1.5-2 m) along horizontal runs to maintain proper slope and prevent sagging.
- Keep the total horizontal pipe length under 65 feet (20 m).
- If installed side-by-side, maintain a gap of approximately 3/8 inch (9.5 mm) between parallel pipes.
Drain Pipe & Insulation Material Requirements
- Drain pipe: Polyvinyl chloride (PVC) pipe with an outer diameter of approximately 1-1/4 inch (32 mm).
- Heat insulation: Foamed polyethylene insulation with a maximum thickness of 3/8 inch (9.5 mm).